Deep Sea DSE4620 Auto Mains (Utility) Failure Control Modules
See Details:
DEEPSEA CONTROLLER DSE4620 are suitable for a wide variety of single gen-set applications.Whilst maintaining functions included within higher end controllers, such as generator or load power monitoring, the DSE45xx range of especially compact controllers provide the user with the ultimate size tofeature ratio.
Monitoring engine speed, oil pressure, coolant temperature, frequency, voltage, current, power and fuel level, the modules will give comprehensive engine and alternator protection. This will be indicated on the largest back-lit LCD icon display in its class via an array of warning, electrical trip andshutdown alarms.
Through USB Communication both modules can be easily configured using the DSE Configuration Suite PC Software or can be fully configured through the module's front panel editor.
All DSE products are supported by the DSE global tech nical support team which gives our customersand end users access to 24 hour system help and advice.
KEY FEATURES:
Ultimate size to feature ratio
Automatically transfers between mains (utility) and generator (DSE4520 only)
Hours counter provides accurate information for monitoring and maintenance periods
User-friendly set-up and button layout for ease of use
Multiple parameters are monitored simultaneously which are clearly displayed on thelargest back-lit icon display inits class
The module can be configured to suit a wide range of applications
Uses DSE Configuration Suite PC Software for simplified configuration
Compatible with a wide range of CAN engines
Licence-free PC software
IP65 rating (with optional gasket) offers increased resistance to water ingress
CONTINUOUS VOLTAGE RATING:8 V to 35 V Continuous
VOLTAGE RANGE:
15 V to 415 V AC (Ph to N) 26 V to 719 V AC (Ph to Ph)
CRANKING DROPOUTS:Able to survive 0 V for 50 mS
FREQUENCY RANGE:3.5 Hz to 75 Hz
MAXIMUM OPERATING CURRENT:85 mA at 12 V, 96 mA at 24 V
MAXIMUM STANDBY CURRENT:51 mA at 12 V, 47 mA at 24 V
VOLTAGE RANGE:
15 V to 415 V AC (Ph to N) 26 V to 719 V AC (Ph to Ph)
MAXIMUM SLEEP CURRENT:35 mA at 12 V, 32 mA at 24 V
FREQUENCY RANGE:3.5 Hz to 75 Hz
OUTPUT A (FUEL):10 A short term, 5 A continuous,at supply voltage
OVERALL:140 mm x 113 mm x 43 mm
OUTPUT B (START):10 A short term, 5 A continuous,at supply voltage
PANEL CUT-OUT:118 mm x92 mm
AUXILIARY OUTPUTS C,D:2 A DC at supply voltage
MAXIMUM PANEL THICKNESS:8 mm